You are now viewing the owner's manual for your Liebert Refrigerator, model number .This guide is designed to help you understand the features, functionalities, and maintenance requirements of your Refrigerator. Remember, your Liebert Refrigerator is not just an appliance; it's an investment in your daily comfort and convenience. Please take a moment to familiarize yourself with this manual to ensure you get the most out of your Liebert Refrigerator.

background image

Process Fluid Chiller Designed for Marconi Medical Eclipse, Polaris, PD100/150, PD200, Apollo          1

Keeping Business in Business

Process Fluid Chiller Designed for Marconi Medical

Eclipse, Polaris, PD100/150, PD200, Apollo

• Dedicated, equipment-matched cooling supplies the proper temperature and water flow year round.
• Factory-tested, piped, wired and charged for hassle-free startup and operation.
• Clean, non-ferrous cooling loop, required for sensitive medical equipment.
• Local service and parts for quick and knowledgeable maintenance and service.
• Optional switch-over to alternate water source provides redundant, continuous operation.
• Optional remote monitoring systems keep you informed of chiller operation.
• UL/CSA certified.
• ISO 9001 certified company. 

Eclipse/Polaris Specifications

Fluid Specified

Glycol

Max Heat Dissipation—BTUH (kW)

75,000 (22)

Fluid Temperature Range—°F (°C)

50-55 (10-13)

Fluid Flow Rate—GPM (l/m)

15.0 (57.0)

Fluid Pressure Drop—PSI (kPa)

65.0 (448.0)

Process Fluid Chiller Specifications

Model Number

PS096A

PS096A

PS096A

Fluid Circulated

Water

Ethylene Glycol

Propylene Glycol

Net Cooling Capacity—BTUH (kW)

83,400 (24.4)

79,000 (23.1)

75,600 (22.2)

Leaving Fluid Temperature—°F (°C)

50 (10)

50 (10)

50 (10)

Fluid Flow Rate—GPM (l/m)

15 (57)

15 (57)

15 (57)

Eclipse/Polaris Pressure Drop—PSI (kPa)

65 (448)

65 (448)

65 (448)

Chiller Pressure Drop—PSI (kPa)

7.6 (52.4)

10.2 (70.3)

12.0 (82.7)

Pump Total Head—PSI (kPa)

86.5 (596.4)

86.5 (596.4)

86.5 (596.4)

Head Available for Piping Circuit—PSI (kPa)

13.9 (95.8)

11.3 (77.9)

9.5 (65.5)

Pump HP (kW)

2 (1.5)

2 (1.5)

2 (1.5)