You are now viewing the owner's manual for your Zanussi Ventilation Hood, model number .This guide is designed to help you understand the features, functionalities, and maintenance requirements of your Ventilation Hood. Remember, your Zanussi Ventilation Hood is not just an appliance; it's an investment in your daily comfort and convenience. Please take a moment to familiarize yourself with this manual to ensure you get the most out of your Zanussi Ventilation Hood.

background image

ZANUSSI

P R O F E S S I O N A L

304 AISI WALL TYPE HOODS

SUPERTREDIL - S line - 1500mm

Net weight - kg.

93

117

136

160

182

203

225

246

Inlet Air Capacity - mc/h

1500

1860

2100

2400

2760

3180

3600

3960

Air Capacity - mc/h

2000

2700

3300

4000

4700

5300

6000

6600

    height

500

500

500

500

500

500

500

500

    depth

1500

1500

1500

1500

1500

1500

1500

1500

    width

1200

1600

2000

2400

2800

3200

3600

4000

External dimensions - mm

STPF1512

641257

STPF1516

641258

STPF1520

641259

STPF1524

641260

STPF1528

641261

STPF1532

641262

STPF1536

641263

STPF1540

641264

CHARACTERISTICS

MODELS

TECHNICAL DATA

RANGE 
COMPOSITION

  

A range of hoods exploiting the 
"inductive emission" principle. 
Untreated air is introduced inside to 
partly compensate for that removed. 
This results in better drawing of 
fumes towards the filter surface and 
reduced air-treatment costs. The 
range consists of hoods with 8 
different lengths (1200, 1600, 2000, 
2400, 2800, 3200, 3600 and 4000 
mm) and 1500 mm deep.

 

FUNCTIONAL AND 
CONSTRUCTION 
FEATURES

 

 

 

Constructed entirely in 304 AISI 

stainless steel.

 

Two separate air circuits 

(extraction and intake) to reduce the 
quantity of treated air released in the 
environment.

 

Rear exhaust with filters and front 

air intake through a narrow slot sized 
to obtain the correct induction effect. 

 

Perforated panel inside the intake 

circuit to guarantee a perfect and 
uniform air distribution.

 

Completely insulated intake area 

to avoid external condensation.

 

Labyrinth filters in 304 AISI 

stainless steel easily removable for 
cleaning. Labyrinth filters guarantee 
constant filtration to avoid clogging 
and protect against fire.

 

Perimetral gutter with drain hole to 

transfer grease into a 304 AISI 
container.

 

External panels with upturned 

edges to avoid injuries. 

 

The outlet holes are sized in order 

to minimize drops in pressure.

 

Pressure gauging for perfect 

calibration.

 

Built-in lighting with protective 

screen.

 

Available, as optional accessory, 

an air intake Plenum, which is 
insulated to avoid condensation.

 

Heating and air conditioning costs 

reduced up to 60%.